Electrical coordination
Confirm rated voltage, MCOV, nominal discharge current and residual-voltage limits against the project study.


Metal oxide surge arrester
FUERTE’s supplier-published ZnO arrester table covers 3–36 kV rated-voltage models with 5 kA and 10 kA nominal discharge-current options and 2.55–29 kV MCOV values.
The supplier page lists IEC60099-4 and IEEE C62.11 as the technical standards; confirm the required edition and project acceptance documents before ordering.
Published technical data
Use the published family table to shortlist rated voltage, nominal discharge current, MCOV and residual-voltage levels before checking the project insulation-coordination study.
| Model | Rated Voltage | Nominal Discharge Current | MCOV | 1/4 μs Lightning Current Impulse | 8/20 μs Lightning Current Impulse | 30/60 μs Swilching Current Impulse | 2ms Reclangular Current Impulse Withstand | 4/10 μs High Current Impulse Withstand |
| kV(rms) | kA | kV(rms) | kV(Cresl) | kV (Crest) | kV (Crest) | A | kA (Crest) | |
| YH5W-3 | 3 | 5 | 2.55 | 11.3 | 9 | 8.9 | 150 | 65 |
| YHIOW-3 | 3 | 10 | 2.55 | 11.3 | 9 | 8.9 | 250 | 100 |
| YH5W-6 | 6 | 5 | 5.1 | 22.6 | 18 | 16.8 | 150 | 65 |
| YH10W-6 | 6 | 10 | 5.1 | 22.6 | 18 | 16.8 | 250 | 100 |
| YH5W-9 | 9 | 5 | 7.65 | 33.7 | 27 | 23.8 | 150 | 65 |
| YH10W-9 | 9 | 10 | 7.65 | 33.7 | 27 | 23.8 | 250 | 100 |
| YH5W-10 | 10 | 5 | 8.4 | 36 | 30 | 26.4 | 150 | 65 |
| YH10W-10 | 10 | 10 | 8.4 | 36 | 30 | 26.4 | 250 | 100 |
| YH5W-11 | 11 | 5 | 9.4 | 40 | 33 | 30 | 150 | 65 |
| YH10W-11 | 11 | 10 | 9.4 | 40 | 33 | 30 | 250 | 100 |
| YH5W-12 | 12 | 5 | 10.2 | 42.2 | 36 | 31.7 | 150 | 65 |
| YH10W-12 | 12 | 10 | 10.2 | 42.2 | 36 | 31.7 | 250 | 100 |
| YH5W-15 | 15 | 5 | 12.7 | 51 | 45 | 38.5 | 150 | 65 |
| YH10W-15 | 15 | 10 | 12.7 | 51 | 45 | 38.5 | 250 | 100 |
| YH5W-18 | 18 | 5 | 15.3 | 61.5 | 54 | 46.2 | 150 | 65 |
| YH10W-18 | 18 | 10 | 15.3 | 61.5 | 54 | 46.2 | 250 | 100 |
| YH5W-21 | 21 | 5 | 17 | 71.8 | 63 | 54.2 | 150 | 65 |
| YH10W-21 | 21 | 10 | 17 | 71.8 | 63 | 54.2 | 250 | 100 |
| YH5W-24 | 24 | 5 | 19.5 | 82 | 72 | 62 | 150 | 65 |
| YH10W-24 | 24 | 10 | 19.5 | 82 | 72 | 62 | 250 | 100 |
| YH5W-27 | 27 | 5 | 22 | 92 | 81 | 69.8 | 150 | 65 |
| YH10W-27 | 27 | 10 | 22 | 92 | 81 | 69.8 | 250 | 100 |
| YH5W-30 | 30 | 5 | 24.4 | 102 | 90 | 79 | 150 | 65 |
| YH10W-30 | 30 | 10 | 24.4 | 102 | 90 | 79 | 250 | 100 |
| YH5W-33 | 33 | 5 | 27.5 | 112 | 99 | 86.7 | 150 | 65 |
| YH10W-33 | 33 | 10 | 27.5 | 112 | 99 | 86.7 | 250 | 100 |
| YH5W-36 | 36 | 5 | 29 | 123 | 108 | 92.4 | 150 | 65 |
| YH10W-36 | 36 | 10 | 29 | 123 | 108 | 92.4 | 250 | 100 |
Confirm the selected rating against the system voltage, earthing arrangement, insulation coordination, installation altitude and pollution conditions.
Checklist seleksi
Configuration and supply boundary
The source describes Grade 304 stainless steel terminal hardware and optional NEMA A or B mounting brackets, earth leads, line clamps, bird guards, disconnectors, discharge counters and monitors.
Confirm rated voltage, MCOV, nominal discharge current and residual-voltage limits against the project study.
State bracket pattern, terminal connection, line clamp and earth-lead requirements in the inquiry.
Confirm whether the supply should include a disconnector, insulating base, counter or monitor.
Quantity, packing, delivery schedule, test documents and destination requirements depend on quotation.



Skala perusahaan
FUERTE mencatat tahun pendiriannya sebagai tahun 1985, dengan 220+ karyawan dan area bangunan seluas 36.000 m². Angka-angka yang dipublikasikan oleh pemasok tersebut memberikan konteks terkait dengan manufaktur dan dukungan proyek.
1985
Supplier-published company history
220+
Published workforce scale
36,000 m²
Published manufacturing footprint
OEM
Subject to technical review
Kemampuan OEM & ODM
FUERTE’s published OEM and ODM scope includes voltage/current adaptation, mounting hardware, nameplates, packaging and shipping marks.
Electrical configurationReview rated voltage, MCOV, discharge current, residual voltage and service conditions.
Hardware selectionConfirm brackets, terminals, disconnectors, bird guards, counters and monitors.
Project documentationState drawing, marking, packing and acceptance-document requirements before quotation.

Pertanyaan yang sering diajukan
The family table lists rated-voltage models from 3 kV through 36 kV.
The published table provides 5 kA and 10 kA model options.
The source lists IEC60099-4 and IEEE C62.11. Confirm the required edition and acceptance scope in the RFQ.
The supplier page lists mounting brackets, an earth lead, a line clamp, a bird guard, a disconnector, a discharge counter and a monitor as selectable items.
Ulasan konfigurasi
Provide system voltage, arrester rated voltage, MCOV, nominal discharge current, residual-voltage limits, mounting and accessory requirements, quantity, destination market and required documents.