Electrical coordination
Confirm rated voltage, current, impulse withstand, power-frequency withstand and leakage distance against the project study.
Medium-voltage isolating switch
GW13-15 Isolating Switch is a medium-voltage isolating switch for outdoor distribution isolation. The supplier table lists 12 / 36 kV rated-voltage options, 400 / 630 A rated-current options and 16(for 400A)/ 20(for 630A) kA rated short-circuit withstand current.
The supplier source lists IEC 62271-102:2001. Confirm the required standard edition, test documents and project acceptance scope before ordering.
Solicite una revisión de la configuraciónBrowse isolating switches
Published technical data
The table below is transcribed from the target model’s authenticated WordPress source. Confirm the selected voltage, current, withstand level and accessory combination in the RFQ.
| Características eléctricas | Especificaciones | Unidad | |
|---|---|---|---|
| Rated voltage of Disconnector | 12 | 36 | kV |
| Corriente nominal | 400 / 630 | A | |
| Rated frequency | 50 | Hz | |
| Lighting Impulse withstand voltage | 95 | 170 | kV |
| Power frequency withstand voltage in 1 min (Dry) | 42 | 70 | kV |
| Power frequency withstand voltage in 10 s (Wet) | 36 | 60 | kV |
| Rated short circuit withstand current | 16(for 400A)/ 20(for 630A) | kA | |
| Rated short circuit withstand time | 3 | s | |
| Rated peak withstand current | 40(for 400A)/ 50(for 630A) | kA | |
| Creepage | 25 | 20 | mm/kV |
| Blade stopped degree in opening position | 90 | Degree | |
| Repuestos | |||
| Suport de montaje | con/sin | ||
| Terminal clamp | con/sin | ||
| Loadbuster Hook | con/sin | ||
| Self locking Mechanism | with | ||
| Material | |||
| Terminal pads | Brass/Copper plated by silver | ||
| Blade | Copper plated by siliver | ||
| Isolador | Porcelain / Polymer | ||
| Channel Base | Steel hot galvanized | ||
| Operating eye | Brass | ||
| Paquete | |||
| Cantidad/paquete | 1 | PC/caja de cartón | |
| Condiciones de servicio | |||
| Temperatura máxima del entorno | 40 | °C | |
| Nivel de contaminación | Heavy | ||
| Altitud | ≤1000 | Métrica | |
| Estándar | IEC 62271-102:2001 | ||
Published source values include 50 Hz, 20 mm, 2001. Confirm the exact row and unit in the original technical table when preparing the RFQ.
Confirm system voltage, earthing arrangement, installation altitude, pollution level and required operating duty with the project engineer before final selection.
Lista de verificación de selección
Configuration and supply boundary
The target source lists selectable hardware and material options. State each option explicitly so the quotation reflects the intended field installation.
Confirm rated voltage, current, impulse withstand, power-frequency withstand and leakage distance against the project study.
Depending on the model, specify operating mechanism, arcing-distinguishing chamber, operating rod length, loadbuster hook or self-locking mechanism.
The source lists silver-plated copper terminals and blades, porcelain or polymer insulators and hot-galvanized steel bases. Confirm the selected combination.
Quantity, packaging, delivery schedule, private label and project documents remain subject to technical review and quotation.



Escala de la empresa
FUERTE menciona el año 1985 como su año de fundación, 220 empleados y una superficie construida de 36.000 m². Estas cifras publicadas por los proveedores proporcionan contexto para la fabricación y el apoyo a los proyectos.
1985
Supplier-published company history
220+
Published workforce scale
36,000 m²
Published manufacturing footprint
OEM
Subject to technical review
Capacidad de OEM y ODM
FUERTE’s published OEM and ODM scope includes voltage/current adaptation, mounting hardware, nameplates, packaging and shipping marks.
Electrical configurationReview rated voltage, current, withstand values and service conditions for the target market.
Hardware selectionConfirm poles, operating mechanism, rod length, brackets, terminals and corrosion-resistant materials.
Project documentationState drawings, marking, packing, shipping marks and acceptance-document requirements before quotation.

Preguntas frecuentes
The target table lists 12 / 36 kV rated-voltage options and 400 / 630 A rated-current options. Confirm the exact configuration in the quotation.
Review impulse withstand, power-frequency withstand, short-circuit withstand current and peak withstand current together with the insulation-coordination study.
The source lists selectable mechanisms, brackets, terminals and, for some models, operating-rod length. Availability depends on technical review.
State model, poles, voltage, current, withstand duty, operating hardware, mounting arrangement, quantity, destination market and required documents.
Revisión de la configuración
Provide system voltage, rated current, short-circuit duty, insulation levels, pole arrangement, operating hardware, mounting details, quantity, destination market and required documents.
¿Está interesado en este producto? Complete el formulario que aparece a continuación y nuestro equipo de ventas se pondrá en contacto con usted dentro de las 24 horas.
No dude en dejar un mensaje para consulta. Le ofreceremos más opciones de servicio.