Fuse tube and holder
The fuse tube uses fiberglass with a synthetic arc-extinguishing liner and a UV-resistant coating. The holder is described as exchangeable.



FSC porcelain fuse cutout series
The FSC porcelain drop out fuse cutout series is designed for outdoor AC distribution systems, where the fuse link operates under overload or short-circuit conditions and the holder drops to provide a visible indication.
The published FSC range covers 10–36 kV with 100 A and 200 A rated-current options. Standard and FSC-( )F loadbreak executions are listed in the supplier source.
The source lists compliance with IEC 60282-2, ANSI C37.41 and ANSI C37.42. Confirm the required edition and project acceptance documents before ordering.
Solicite una revisión de la configuración Explora los recortes de los fusibles
Construction and operation
The supplier source describes the conductive path, fuse-tube construction and selectable hardware. Match each option to the utility specification rather than treating every feature as standard.
The fuse tube uses fiberglass with a synthetic arc-extinguishing liner and a UV-resistant coating. The holder is described as exchangeable.
The top contact is a silver-coated red-copper strip, while the hinge uses bronze and silver-plated copper-alloy contacts.
A silver-plated copper arc-shortening rod is available; when this option is used, the source requires a fuse link with a removable button head.
Choose NEMA A, NEMA B or an extended galvanized-steel mounting bracket for the project crossarm. Stainless-steel hood, loadbreak hooks and hardware are listed as corrosion-resistance options.
The supplier source states a mechanical life of more than 3,000 opening and closing operations. Treat this as supplier-stated data until the applicable test method and report are confirmed.
Model selection
Rated and breaking currents are paired by row. Electrical values below reproduce the target product’s published table; final coordination remains the buyer’s engineering responsibility.
| Model | Rated Voltage | Rated Current | Breaking Current | Impulse Withstand Voltage Across Gaps | Power-frequency Withstand Voltage | Leakage Distance | |
| kV | A | A | kA | kV BIL | kV | mm | |
| FSC-1 | 10~15kV | 100 | 300 | 10 | 110 | 40 | 230 |
| 200 | 12 | ||||||
| FSC-12 | 15~27kV | 100 | 300 | 8 | 125 | 45 | 320 |
| 200 | 12 | ||||||
| FSC-18 | 24~27kV | 100 | 300 | 8 | 150 | 65 | 520 |
| 200 | 10 | ||||||
| FSC-21 | 33~36kV | 100 | 300 | 6 | 170 | 70 | 660 |
| 200 | 8 | ||||||
| FSC-22 | 33~36kV | 100 | 300 | 6 | 170 | 70 | 720 |
| 200 | 8 | ||||||
| FSC-23 | 33~36kV | 100 | 300 | 6 | 170 | 70 | 680 |
| 200 | 8 |
The original specification table contains an unlabeled 300 A column. Its meaning is not published, so confirm whether it refers to the optional disconnect blade before using it in a purchase specification.
Lista de verificación de selección
Configuration boundaries
The source also describes a silicone-rubber polymer support that has passed a 1,000-hour salt-spray test. Because this page is for the porcelain series, confirm the required support material before quotation.
A 300 A disconnect blade is listed as an option for disconnecting service. Confirm its relationship to the unlabeled 300 A table column and the selected standard or loadbreak execution.




Escala de la empresa
FUERTE menciona el año 1985 como su año de fundación, 220 empleados y una superficie construida de 36.000 m². Estas cifras publicadas por los proveedores proporcionan contexto para la fabricación y el apoyo a los proyectos.
1985
Décadas de historia en la fabricación
220+
Personal cualificado y ingenieros experimentados
36k m²
Rastros de fabricación publicados por el proveedor
OEM
La personalización está sujeta a la revisión del proyecto
Capacidad de OEM y ODM
FUERTE’s published OEM and ODM scope includes voltage/current adaptation, mounting hardware, nameplates, packaging and shipping marks. The company also states that it develops customized solutions from technical drawings, market standards and project requirements.
Personalización completaEtiquetado privado, ajuste de especificaciones, desarrollo de muestras y producción en masa.
Experiencia internacionalFUERTE afirma que ha entregado más de 100 diseños personalizados a Estados Unidos, Arabia Saudita, Kenia, Sudáfrica, Tailandia y otros mercados.
Suporte entre categoríasSe enumeran las adaptaciones para los recortes de fusibles, los disipadores de rayos, los interruptores de aislamiento y los accesorios relacionados.

Preguntas frecuentes
The published table covers 10–36 kV across FSC-1, FSC-12, FSC-18, FSC-21, FSC-22 and FSC-23. Use the individual row to confirm current, breaking duty and insulation values.
The source describes the standard type as usable for overhead disconnecting service and identifies FSC-( )F as the porcelain loadbreak version. Confirm the blade and hook arrangement for the selected model.
The supplier source requires a fuse link with a removable button head when the arc-shortening rod is used.
Confirm model, execution, bracket, fuse-link arrangement, quantity and destination market in the quote request. Include the applicable standard edition and project test-document requirements.
Revisión de la configuración
For an accurate review, provide system voltage, continuous current, required breaking duty, BIL, power-frequency withstand, leakage distance, mounting bracket, fuse-link arrangement, order quantity and destination market.
¿Está interesado en este producto? Complete el formulario que aparece a continuación y nuestro equipo de ventas se pondrá en contacto con usted dentro de las 24 horas.
No dude en dejar un mensaje para consulta. Le ofreceremos más opciones de servicio.