Fuse tube and holder
The fuse tube uses fiberglass with a synthetic arc-extinguishing liner and a UV-resistant coating. The holder is described as exchangeable.



FSC porcelain fuse cutout series
The FSC porcelain drop out fuse cutout series is designed for outdoor AC distribution systems, where the fuse link operates under overload or short-circuit conditions and the holder drops to provide a visible indication.
The published FSC range covers 10–36 kV with 100 A and 200 A rated-current options. Standard and FSC-( )F loadbreak executions are listed in the supplier source.
The source lists compliance with IEC 60282-2, ANSI C37.41 and ANSI C37.42. Confirm the required edition and project acceptance documents before ordering.
Demander une révision de la configuration Parcourir les coupe-circuits à fusibles
Construction and operation
The supplier source describes the conductive path, fuse-tube construction and selectable hardware. Match each option to the utility specification rather than treating every feature as standard.
The fuse tube uses fiberglass with a synthetic arc-extinguishing liner and a UV-resistant coating. The holder is described as exchangeable.
The top contact is a silver-coated red-copper strip, while the hinge uses bronze and silver-plated copper-alloy contacts.
A silver-plated copper arc-shortening rod is available; when this option is used, the source requires a fuse link with a removable button head.
Choose NEMA A, NEMA B or an extended galvanized-steel mounting bracket for the project crossarm. Stainless-steel hood, loadbreak hooks and hardware are listed as corrosion-resistance options.
The supplier source states a mechanical life of more than 3,000 opening and closing operations. Treat this as supplier-stated data until the applicable test method and report are confirmed.
Model selection
Rated and breaking currents are paired by row. Electrical values below reproduce the target product’s published table; final coordination remains the buyer’s engineering responsibility.
| Model | Rated voltage (kV) | Rated current (A) | Breaking current (kA) | Impulse withstand across gaps (kV BIL) | Power-frequency withstand (kV) | Leakage distance (mm) |
|---|---|---|---|---|---|---|
| FSC-1 | 10–15 | 100 | 10 | 110 | 40 | 230 |
| FSC-1 | 10–15 | 200 | 12 | 110 | 40 | 230 |
| FSC-12 | 15–27 | 100 | 8 | 125 | 45 | 320 |
| FSC-12 | 15–27 | 200 | 12 | 125 | 45 | 320 |
| FSC-18 | 24–27 | 100 | 8 | 150 | 65 | 520 |
| FSC-18 | 24–27 | 200 | 10 | 150 | 65 | 520 |
| FSC-21 | 33–36 | 100 | 6 | 170 | 70 | 660 |
| FSC-21 | 33–36 | 200 | 8 | 170 | 70 | 660 |
| FSC-22 | 33–36 | 100 | 6 | 170 | 70 | 720 |
| FSC-22 | 33–36 | 200 | 8 | 170 | 70 | 720 |
| FSC-23 | 33–36 | 100 | 6 | 170 | 70 | 680 |
| FSC-23 | 33–36 | 200 | 8 | 170 | 70 | 680 |
The original specification table contains an unlabeled 300 A column. Its meaning is not published, so confirm whether it refers to the optional disconnect blade before using it in a purchase specification.
Liste de contrôle de sélection
Configuration boundaries
The source also describes a silicone-rubber polymer support that has passed a 1,000-hour salt-spray test. Because this page is for the porcelain series, confirm the required support material before quotation.
A 300 A disconnect blade is listed as an option for disconnecting service. Confirm its relationship to the unlabeled 300 A table column and the selected standard or loadbreak execution.

Taille de l'entreprise
FUERTE indique 1985 comme année de fondation, plus de 220 employés et une superficie bâtie de 36 000 m². Ces chiffres publiés par le fournisseur fournissent un contexte pour la fabrication et le support de projets.
1985
Des décennies d'histoire manufacturière
220+
Personnel qualifié et ingénieurs expérimentés
36k m²
Empreinte de fabrication publiée par le fournisseur
OEM
Personnalisation soumise à l'examen du projet
Capacité OEM & ODM
FUERTE’s published OEM and ODM scope includes voltage/current adaptation, mounting hardware, nameplates, packaging and shipping marks. The company also states that it develops customized solutions from technical drawings, market standards and project requirements.
Personnalisation complèteMarque de distributeur, ajustement des spécifications, développement d'échantillons et production en série.
Expérience internationaleFUERTE déclare avoir livré plus de 100 conceptions personnalisées aux États-Unis, en Arabie saoudite, au Kenya, en Afrique du Sud, en Thaïlande et sur d'autres marchés.
Support inter-catégoriesLes adaptations sont répertoriées pour les coupe-circuits à fusibles, les parafoudres, les sectionneurs et les accessoires associés.

Foire aux questions
The published table covers 10–36 kV across FSC-1, FSC-12, FSC-18, FSC-21, FSC-22 and FSC-23. Use the individual row to confirm current, breaking duty and insulation values.
The source describes the standard type as usable for overhead disconnecting service and identifies FSC-( )F as the porcelain loadbreak version. Confirm the blade and hook arrangement for the selected model.
The supplier source requires a fuse link with a removable button head when the arc-shortening rod is used.
Confirm model, execution, bracket, fuse-link arrangement, quantity and destination market in the quote request. Include the applicable standard edition and project test-document requirements.
Examen de la configuration
For an accurate review, provide system voltage, continuous current, required breaking duty, BIL, power-frequency withstand, leakage distance, mounting bracket, fuse-link arrangement, order quantity and destination market.
Ce produit vous intéresse ? Remplissez le formulaire ci-dessous et notre équipe commerciale vous recontactera dans les 24 heures.
N'hésitez pas à laisser un message pour consultation. Nous vous proposerons davantage d'options de service.