Electrical coordination
Confirm rated voltage, MCOV, nominal discharge current and residual-voltage limits against the project study.

Metal oxide surge arrester
The supplier table identifies Y5(10)W-15 / Y5(10)C-15 as a 15 kV, 50 Hz, gapless Design B distribution-type surge arrester with 5 / 10 kA nominal discharge-current options and 12.7 kV maximum continuous operating voltage.
The source lists IEC60099-4:2014. Confirm the required standard edition, arrester class and project acceptance documents before ordering.
Demander une révision de la configurationBrowse lightning arresters
Published technical data
Review the published electrical characteristics together with the selectable accessories, material options, package information and service conditions.
| Paramètre | Published value | Unité |
|---|---|---|
| Rated voltage of Surge arrreser | 15 | kV |
| Nominal discharge current | 5 / 10 | kA |
| Fréquence assignée | 50 | Hz |
| Maximum continuous operating voltage | 12.7 | kV |
| Steep current impulse residual voltage | 51 | kV(Crest) |
| Lightning Impulse residual voltage | 45 | kV(Crest) |
| Switching Impulse residual voltage | 38.5 | kV(Crest) |
| Long duration current impulse withstand voltage | 150 / 250 | A |
| High current impulses | 65 / 100 | kA (Crest) |
| Rated Short-circuit current | 20 / 12 / 6 / 0.6 ± 0.2 | kA |
| Class of Surge arrester | Class 1 or Class 2 | |
| Application | Distribution type | |
| With or without gap | Gapless | |
| Designation of arrester | Design B | |
| Pièces de rechange | ||
| NEMA A or B mounting bracket | with/without | |
| Disconnector | with/without | |
| Earth lead | with/without | |
| Bird guard cap | with/without | |
| Line clamp | with/without | |
| Upper terminal (incoming line) bolt size | M12 | |
| Lower termina (outgoing line) bolt size | M10 | |
| Material | ||
| Upper terminal | Stainless steel 304 | |
| Housing | Polymer type | |
| Color of housing | Dark grey / light grey | |
| Varistor | High quality zinc oxide varistor | |
| Size of Varistor | 35mm / 38mm /40mm / 42mm | |
| Package | ||
| Qty/package | 3 | pc/carton |
| Service conditions | ||
| Environment maximum temperature | 40 | ℃ |
| Pollution level | Heavy | |
| Altitude | 1000 | Meter |
| Standard | IEC60099-4:2014 | |
Confirm the selected rating against the system voltage, earthing arrangement, insulation coordination, installation altitude and pollution conditions.
Liste de contrôle de sélection
Configuration and supply boundary
The supplier table lists a polymer housing, Grade 304 stainless steel upper terminal and zinc oxide varistor options sized 35mm / 38mm /40mm / 42mm.
Confirm rated voltage, MCOV, nominal discharge current and residual-voltage limits against the project study.
State bracket pattern, terminal connection, line clamp and earth-lead requirements in the inquiry.
Confirm whether the supply should include a disconnector, insulating base, counter or monitor.
Quantity, packing, delivery schedule, test documents and destination requirements depend on quotation.
Taille de l'entreprise
FUERTE indique 1985 comme année de fondation, plus de 220 employés et une superficie bâtie de 36 000 m². Ces chiffres publiés par le fournisseur fournissent un contexte pour la fabrication et le support de projets.
1985
Supplier-published company history
220+
Published workforce scale
36,000 m²
Published manufacturing footprint
OEM
Subject to technical review
Capacité OEM & ODM
FUERTE’s published OEM and ODM scope includes voltage/current adaptation, mounting hardware, nameplates, packaging and shipping marks.
Electrical configurationReview rated voltage, MCOV, discharge current, residual voltage and service conditions.
Hardware selectionConfirm brackets, terminals, disconnectors, bird guards, counters and monitors.
Project documentationState drawing, marking, packing and acceptance-document requirements before quotation.

Foire aux questions
The table lists 15 kV rated voltage and 12.7 kV maximum continuous operating voltage.
The published steep-current, lightning-impulse and switching-impulse residual voltages are 51 kV, 45 kV and 38.5 kV crest respectively.
The source identifies the product as a gapless, Design B, distribution-type arrester.
State the system voltage, MCOV, nominal discharge current, residual-voltage limits, short-circuit requirement, mounting hardware, disconnector, terminal sizes, quantity and destination market.
Examen de la configuration
Provide system voltage, arrester rated voltage, MCOV, nominal discharge current, residual-voltage limits, mounting and accessory requirements, quantity, destination market and required documents.
Ce produit vous intéresse ? Remplissez le formulaire ci-dessous et notre équipe commerciale vous recontactera dans les 24 heures.
N'hésitez pas à laisser un message pour consultation. Nous vous proposerons davantage d'options de service.